Cummins Genset EL450S3(E3), EL500S3(E3)
| Model |
EL450S3(E3) |
EL500S3(E3) |
| Rated frequency |
Hz |
50 |
60 |
50 |
60 |
| Rated output |
KVA/KW |
450/360 |
512/410 |
500/400 |
563/450 |
| Max. output |
KVA/KW |
500/400 |
563/450 |
563/450 |
625/500 |
| Rated voltage |
V |
400/230 |
416/240 |
400/230 |
416/240 |
| Rated current |
A |
649.5 |
710.6 |
721.7 |
781.4 |
| Rated speed |
rpm |
1500 |
1800 |
1500 |
1800 |
| Circulated Type |
Three-phase,four wires Y type connection |
| Excitation Mode |
Brushless self-excitation and constant voltage(AVR) |
| Engine Type |
CUMMINS |
| Engine model |
KTA19-G3 |
KTA19-G4 |
| Engine type |
Liquid Cooled,IN-line,6 Cylinder,Four stroke |
| Rated power(KW) |
403 |
463 |
448 |
507 |
| Max power(KW) |
448 |
511 |
504 |
563 |
| Cylinder NO. –bore × Stroke |
mm |
6-159x159 |
6-159x159 |
| Displacement |
L |
18.9 |
18.9 |
| Compression ratio |
18 |
| Alternator Manufacturer |
Leroy Somer or Stamford |
| Phase NO. |
3-phase |
| Power Factor |
0.8(lag) |
| Voltage Adjusting Range |
>=+/-6% |
| Insulation grade |
H |
| Protection Class |
IP23 |
| Pole number |
4 |
| Lubrication system |
Combined Pressure & Splashing |
| Starting system |
Electric start |
| Fuel type |
0#(summer) -10#(winter) -20#(chillness) diesel |
| Lube oil brand |
CD grade or SAE10W-30, 15W-40 |
| Capacity of cooling water |
L |
30 |
30 |
| Lube capacity |
L |
42 |
42 |
| Starting motor capacity |
V-kW |
24V-21.6KW |
24V-21.6KW |
24V-21.6KW |
24V-21.6KW |
| Charging generator capacity |
V-W |
24V-840W |
24V-840W |
24V-840W |
24V-840W |
| Battery capacity |
V-Ah |
2-12V-120AH |
2-12V-120AH |
2-12V-120AH |
2-12V-120AH |
| Fuel consumption |
g/kW.h |
≤ 210 |
≤ 210 |
| Fuel tank capacity |
L |
675 |
675 |
| Continuous running time |
Hr |
8 |
8 |
| Structure Type |
S:Ultra silent E:Open Frame |
| Overall dimension: L×W×H |
mm |
4500x1700x2400 |
4500x1700x2400 |
Related Products
Other Products

- ELECAL Canopy GensetELECAL canopy genset is a kind of water cooled generator produced by Changhua. Our ELECAL canopy ...